1. The unit shall have an
Aluminum tubing system with Aluminum intermediate supports.
2. The floor of the unit
shall be of Aluminum checker plate and insulated with a minimum of 2
insulation.
3. The walls of the unit
shall be constructed of 2 thick polystyrene insulation with 26 gauge
galvanized construction. The Color shall be white.
4. Units that are shipped
in several sections shall be bolted together with neoprene gasket in
between creating an air tight seal.
5. The cooling coil drain
pans shall be insulated with Arm-Flex and made of 304L stainless steel
double sloped allowing the condensate to fully drain out. The drain
connection shall be a minimum 1 ź.
6. Stacked cooling coils
shall have a 304L stainless steel intermediate drain pan draining to
the lower drain pan with a minimum 1 drain.
7. All coil connections
shall be outside the unit casing.
8. The coils shall be individually
removable. Cooling coils shall be mounted on stainless steel track and
heating coils mounted on mild steel angle painted with rust inhibitor
paint. The coils will need to be supported when removed from the air
handler.
9. Indirect cooling coils
shall have cleanable return bends and seat connections.
10. Air Blenders shall be
constructed of galvanized steel painted with rust inhibitor paint.
11. Pre and Final Filters
shall be face load in galvanized steel frames. Suitable for AAF of Farr
filters.
12. The mixing section shall
have low leak parallel blade dampers constructed of Aluminum.
13. Access doors shall be
hinged and lockable with Arosio style hinges, 210 Ventlok handles, locking
hasp bulb gasket and round viewing window.
14. Each access section
shall have a Vapor tight marine light with one common backlit toggle
light switch at the filter section. The wire for the marine lights shall
be run in rigid conduit.
15. The filter section shall
have a Magnehelic filter gauge, Dwyer, Series 2000, Model #: 2003, range
0 to 3wc.
16. Fan and motors shall
be solidly mounted on a frame.
17. Motors shall be inverter
duty motors.
18. Ahu-1 Unit shall have
direct evaporative cooling. The media shall be Glas-Dek. The evaporative
cooling section shall have a 304L stainless steel with a 12 deep tank
and enclosure, water pump, float valve, make-up water connection, drain
connection, overflow connection and quick fill connection. Sump pump
shall have a disconnect.