Supply Fan Analysis:
Unit : East Mechanical Penthouse Each Fan : 38,500 cfm External Static Pressure : 2.20 wc Internal Static Pressure
Outside Air Louver : 0.10” wc Outside Air Damper : 0.10” wc Mixing Section : 0.10” wc Filters : 0.60” wc Heating Coil : 0.21” wc Direct Expansion Coil : 0.91” wc Inlet Silencer : 0.25” wc Outlet Silencer : 0.25” wc Total Static Pressure : 4.72” wc
Corrected T.S.P @ 5300ft. altitude : 3.78”wc
Fan Selection : (2) 42D5 Twin City - 1800 rpm Fan Efficiency : 80 % Fan BHP : 28.6 Hp Motor Size : 30 H
|
Return Fan Analysis Unit:
East Mechanical Penthouse Total Airflow : 69,300 cfm Each Fan : 23,100 cfm External Static Pressure : 0.75” wc Internal Static Pressure Inlet Silencer : 0.25” wc Outlet Silencer : 0.25” wc Plenum Loss : 0.35” wc Total Static Pressure : 1.60” wc
Correction Factor Ratio : .80” wc
Corrected T.S.P @ 5300ft. altitude : 1.28”wc
Fan Selection : (3) 36D5 TCVA - 1170 rpm Fan Efficiency : 66 % Fan BHP : 7.1 Hp Motor Size : 10 Hp per fan
|