Supply Fan Analysis:

Unit : East Mechanical Penthouse
Each Fan : 38,500 cfm
External Static Pressure : 2.20 wc
Internal Static Pressure

Outside Air Louver : 0.10” wc
Outside Air Damper : 0.10” wc
Mixing Section : 0.10” wc
Filters : 0.60” wc Heating Coil : 0.21” wc
Direct Expansion Coil : 0.91” wc
Inlet Silencer : 0.25” wc
Outlet Silencer : 0.25” wc
Total Static Pressure : 4.72” wc

Corrected T.S.P @ 5300ft. altitude : 3.78”wc

Fan Selection : (2) 42D5 Twin City - 1800 rpm
Fan Efficiency : 80 %
Fan BHP : 28.6 Hp
Motor Size : 30 H

Return Fan Analysis Unit:

East Mechanical Penthouse
Total Airflow : 69,300 cfm
Each Fan : 23,100 cfm
External Static Pressure : 0.75” wc
Internal Static Pressure

Inlet Silencer : 0.25” wc
Outlet Silencer : 0.25” wc
Plenum Loss : 0.35” wc
Total Static Pressure : 1.60” wc

Correction Factor Ratio : .80” wc

Corrected T.S.P @ 5300ft. altitude : 1.28”wc

Fan Selection : (3) 36D5 TCVA - 1170 rpm
Fan Efficiency : 66 %
Fan BHP : 7.1 Hp
Motor Size : 10 Hp per fan



Supply Sound Data:

Supply Fan Lw: 108db  
Discharge Side
 
63
125
250
500
1000
2000
4000
8000
Fan
12
10
4
6
8
12
18
24
Diffuser
3
10
16
20
17
14
12
10
Absorber
15
16
21
24
26
28
26
23
Plenum
8
8
8
9
9
9
9
9
Lw Riser
70
64
59
49
48
45
43
41
Inlet Side
 
63
125
250
500
1000
2000
4000
8000
Fan
17
11
4
6
8
12
18
24
Trap
8
12
23
26
25
19
16
13
Plenum
8
8
8
9
9
9
9
9
Lw Louvers
75
77
73
67
66
68
65
61

Return Sound Data:

Return Fans Lw: 102db
Discharge Side
 
63
125
250
500
1000
2000
4000
8000
Fan
17
14
6
4
8
12
18
24
Absorber
15
16
21
24
26
28
26
23
Plenum
8
8
8
9
9
9
9
9
Lw Riser
61
64
67
66
60
54
50
47
Inlet Side
 
63
125
250
500
1000
2000
4000
8000
Fan
17
11
4
6
8
12
18
24
Trap
2
9
15
18
17
14
14
14
Diffuser
7
12
16
28
35
25
28
17
Lw Louvers
81
71
65
52
42
41
42
47